Digital Multimeters
Volt Tester
KP1
CAT.IV Volt tester
Calibration available products
Calibration available products
- Self test-checking failures of LCD, disconnection of a lead wire
- EF(Electric Field)detection
- LCD with backlight & LED Light for dark place
- Auto data hold
- Auto power off(1min.)
- Auto identification of AC or DC voltage
- True RMS (True root-mean-square value)
- True RMS value. AC current and voltage of a non-sine wave can be measured by true RMS values.
- Continuity buzzer
- The buzzer sounds when the measuring object is electrically conducting.
- EF function
- Non-contact AC voltage detection
- Auto power off
- Power is automatically turned off when a certain time has elapsed after power-up. Some models have a function to cancel this function.
- Data hold
- A value indicated on the display is fixed. It is fixed even after the test lead is removed, and can be used as a record for reference purposes.
- Backlight
- Allows indicator reading in a dark place.
Move your mouse pointer over or click on an icon to see a description of the icon.
Specifications
KP1 | Measuring range | Best accuracy | Resolution |
---|---|---|---|
DCV | 5~999.9V | ±(0.7%+5) | 0.1V |
ACV | 5~999.9V | ±(1.7%+5) | 0.1V |
Continuity | Buzzer sounds at between 20kΩ and 500kΩ Open voltage:approx.0.6V | ||
EF Detection | A voltage of electric field of about 60V or more is detected. The bar graph and intermittant buzzer beeps change in five steps |
Display | numeral display 9999 |
Sampling rate | 6 times/sec.(ACV), 5 times/sec.(DCV) |
Bandwidth | 45~400Hz |
Battery | LR03×2 |
Battery life | Approx.20h |
Size/Mass | H130×W90×D30mm/approx.205g |
Safety | IEC61010 CAT. Ⅳ 600 V/CAT. Ⅲ 1000 V |
※When measuring voltage, less than 5 V will not be detected.
※TL-37 is required when using the adapter on the + side (breaker pin side).